I need to rack and stack Cisco Nexus 93180yc FX3 in my datacenter, therefore, I need to know what airflow mode to choose.
The Nexus 9K datacenter switches support two airflow modes
- Portside intake - sucks cold air into network ports and blows warm air out of the power supply's into hot aisle ( red release latch on hot-swap PSU)
- Portside exhaust - sucks cold air into power supply's and blows warm air out of the ports into hot aisle ( blue release latch on hot-swap PSU)